400v 890C Series Common DC Bus Adapter
Parker 890CA 50A
The 890 CA
Parker SSD 890 Series 50A Common DC Bus Adapter unit for use with 890 series Inverters. Designed for use as part of an 890 Common DC Bus system and provides DC+ and DC- terminal connections allowing flexible wiring between rows of busbar-connected Inverters.
Download Manual Here
The manual can be downloaded here: AC890 Modular Systems Manual
Accessories and Options
NEW Format for 890 Drives
All 890's will now be shipped as bare Drives, no factory fitted modules or options will be available, you will need to order these and fit in whichever format you require before using your drive.
Features
With Power supplies up to 90kW these drives are suitable for use with all common 890 Series feedback and communication options. Alldrives include a USB programming port. If you require a higher power, please see the 890SD series which can be supplied by a DC bus.
Specification
Technical SpecificationsElectrical Characteristics
Operating Temperature | 0 ºC to +45 ºC |
---|---|
Storage Temperature | -25 ºC to +55 ºC |
Enclosure Rating |
IP20 - UL (c-UL) Open Type (North America/Canada) Type 1 Suitable for cubicle mount only |
Cubicle Installation |
The 890 must be installed to EN60204 Standard in the cubicle. For USA, the cubicle shall meet the requirements of UL50. |
Humidity | Maximum 85% relative humidity at 40 Degrees C non-condensing |
Vibration |
The product has been tested to the following specification: Test Fc of EN60068-2-6 10 Hz<=f<=57 Hz sinusoidal 0.075 mm amplitude 57 Hz<=f<=150 Hz sinusoidal 1 g 10 sweep cycles per axis on each of three mutually perpendicular axis |
Atmosphere | Non Flammable, non corrosive and dust free |
EMC Compatibility | CE Marked in accordance with 2004/108/EC |